Nefit, Buderus · Gas boiler - Nefit Topline, Buderus Logamax plus GB 162, Buderus Logano plus GB202
The products pose a risk of fire because, due to overheating of the burner seal, a leakage can occur between the burner housing and the heat exchanger. Through this opening flue gases can flow into the appliance. These flue gases can, after a period of time, lead to fire damage in or outside the appliances. The product does not comply with the Gas Appliances Directive.
- Published
- 27 March 2009
- Notifying authority
- The Netherlands
- Catalog checked
- 30 July 2026
Check the authority measure and original alert.
Type of economic operator taking notified measure(s): Other. Category of measure(s): Voluntary stop of sales and corrective actions.. Date of entry into force: Unknown
Official source alertProduct identification
- Safety Gate reference
- 0392/09
Classification
- Category
- Gas appliances and components
- Risk type
- Fire
- Country of origin
- The Netherlands
Product description
<a href="http://ec.europa.eu/consumers/safety/rapex/docs/0392_09.pdf" target="_blank"> see attachment</a><img src="http://ec.europa.eu/consumers/images/pdf.gif" border="0"/>Gas boiler