EU Safety Gate · Report-2015-050
BetaPlus · Phenolic pipe section
Persons in commercial building where product is used are not able to escape from the building because the reaction to fire properties of the product is D or worse (if not fitted correctly) when claimed to be class B. Thus the product does not slow down the spread of fire in the building, particularly in any open emergency escape stairways with exposed HVAC (heating, ventilation, and air conditioning) piping.
- Published
- 18 December 2015
- Notifying authority
- United Kingdom
- Catalog checked
- 30 July 2026
Check the authority measure and original alert.
Type of economic operator taking notified measure(s): Manufacturer. Category of measure(s): -. Date of entry into force: 01/09/2015
Official source alertProduct identification
- Safety Gate reference
- A11/0116/15
- Model
- Pipe insulation diameters 15mm to 300mm
- Batch
- All CE marked product manufactured from 1 July 2013 to 10 June 2015
Classification
- Category
- Construction products
- Risk type
- Fire
- Country of origin
- United Kingdom
Product description
Thermal foam pipe insulation coated with aluminium foil that is glued to the foam to provide a vapour barrier and is chemically coated. The insulation is used for heating, ventilation and air conditioning, and is suitable for copper, steel and plastic pipe work. Supplied in a cardboard box.